Fire suppression control units and accessories
Mircom’s FR-320 is a dual releasing special hazard suppression control unit that is field configurable for use on Deluge Sprinkler Systems, Pre-Action Sprinkler Systems and Agent Release Systems. The mode of operation is easily configured by selecting one of 14 pre-configured modes of operation. The simple configuration process is done via the front panel and requires no laptop or complicated programming.





<!-- Google Tag Manager -->
<script>(function(w,d,s,l,i){w[l]=w[l]||[];w[l].push({'gtm.start':
new Date().getTime(),event:'gtm.js'});var f=d.getElementsByTagName(s)[0],
j=d.createElement(s),dl=l!='dataLayer'?'&l='+l:'';j.async=true;j.src=
'https://www.googletagmanager.com/gtm.js?id='+i+dl;f.parentNode.insertBefore(j,f);
})(window,document,'script','dataLayer','GTM-WTPZ2M9');</script>
<!-- End Google Tag Manager -->
<!-- Google Tag Manager (noscript) -->
<noscript><iframe src="https://www.googletagmanager.com/ns.html?id=GTM-WTPZ2M9"
height="0" width="0" style="display:none;visibility:hidden"></iframe></noscript>
<!-- End Google Tag Manager (noscript) -->
-
Listed to UL 864, 9th edition
-
Suppression control panel is field configurable to operate with a Deluge Sprinkler System, a Pre-action Sprinkler System and an Agent Release System
-
Six Class B (Style B) Input Circuits
-
Input Circuits One to Four can be configured as Non-Verified Alarm, Non Latching Supervisory, Latching Supervisory or Agent Release/Water Flow depending on the Mode of Operation selected
-
Input Circuits Five & Six can be configured as Manual Release Input, Abort Input or Abort/Manual Release Combination Input depending on the Mode of Operation selected
-
Input Circuits can be converted to Class "A" (Style "D") using the ICAC-306 Converter Module
-
Four Class "B" (Style "Y") Output Circuits which can be configured for Silenceable Signal, Non-Silenceable Signal, Silenceable Strobe, Non-Silenceable Strobe or Releasing Circuit (Circuits 3 & 4 Only)
-
Output Circuits can be converted to Class "A" (Style "Z") using the OCAC-304 Converter Module
-
5 Amp Power Supply
-
4-wire smoke power 22.3 VDC @ 300ma max.Supervised Aux Power 22.3 VDC @ 500ma max.
-
Aux Power (Unregulated) 24 VDC @ 1.7 Amp max.
-
Relay contacts for Common Alarm (Non Disconnectable), Auxiliary Alarm (Disconnectable), Common Supervisory (can be converted to common alarm if no Supervisory input) and Common Trouble
-
Cross Zone option
-
Counting Zones option
-
Output signals can be configured for Steady (fixed) or Escalating (tone changes as input operation changes)
-
Release Timer 0 to 60 Seconds (5 second increments)
-
Manual Release Delay 0 to 30 Seconds (5 second increments)
-
Soak Timer 0 to 15 Minutes (21 Intervals)
-
Abort Release Timer (Standard UL Type Delay, IRL Type Delay, NYC Type Delay, Local Jurisdiction Delay)
-
Special Releasing Power Supply and Release Activation Considerations preventing false dumps
-
Configurable to perform two hazard areas
-
Simple panel programming through 14 Pre- Configured Modes of Operations